Shopping List
Shopping List
USD - US$
Image
/
/
/
/
Schneider Electric C25F42D250 Circuit Breaker Compact NSX250F, 36kA at 415VAC, Micrologic 2.2 Trip Unit 250A, 4 Poles 4d
Schneider Electric C25F42D250 Circuit Breaker Compact NSX250F, 36kA at 415VAC, Micrologic 2.2 Trip Unit 250A, 4 Poles 4d
Image
Image
Specifications
infotip-icon
View other Circuit Breaker dimensions or variations
Please select at least one specification below.
Ambient air temperature for operation
-25…70 °C
Poles Description
4P
Protected Poles Description
4D 3D + N/2 3D
Network Type
AC
[In] Rated Current
250 A at 40 °C
Network Frequency
50/60 Hz
Standards
EN/IEC 60947
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage
8 kV
Ip Degree Of Protection
IP40 conforming to IEC 60529
Pollution Degree
3 conforming to IEC 60664-1
Ambient Air Temperature For Storage
-50…85 °C
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Rating
250 A at 40 °C
Trip Unit Technology
Electronic
This spec is not available in the specification table.
Trip Unit Protection Functions
LSoI
This spec is not available in the specification table.
Control Type
Toggle
This spec is not available in the specification table.
Mounting Mode
Fixed
This spec is not available in the specification table.
Trip Unit Name
MicroLogic 2.2
This spec is not available in the specification table.
Device Short Name
NSX250F
This spec is not available in the specification table.
Product Or Component Type
Circuit breaker
This spec is not available in the specification table.
Range
ComPacT new generation
This spec is not available in the specification table.
Product Name
ComPacT NSX new generation
This spec is not available in the specification table.
Device Application
Distribution
This spec is not available in the specification table.
Connection Pitch
35 mm
This spec is not available in the specification table.
Neutral Position
Left
This spec is not available in the specification table.
Utilisation Category
Category A
This spec is not available in the specification table.
Suitability For Isolation
Yes conforming to EN/IEC 60947-2
This spec is not available in the specification table.
Mounting Support
Backplate
This spec is not available in the specification table.
Local Signalling
Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
This spec is not available in the specification table.
Mechanical Durability
20000 cycles
This spec is not available in the specification table.
Electrical Durability
20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
This spec is not available in the specification table.
Earth-Leakage Protection
Without
This spec is not available in the specification table.
Product Certifications
CCC Marine EAC
This spec is not available in the specification table.
Ik Degree Of Protection
IK07 conforming to IEC 62262
This spec is not available in the specification table.
Protection Type
L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
This spec is not available in the specification table.
Upside Connection
Front
This spec is not available in the specification table.
Downside Connection
Front
This spec is not available in the specification table.
Electrical Shock Protection Class
Class II
This spec is not available in the specification table.
Thermal Memory
20 minutes before and after tripping
This spec is not available in the specification table.
Performance Level
F 36 kA 415 V AC
This spec is not available in the specification table.
Number Of Slots For Electrical Auxiliaries
5 slot(s)
This spec is not available in the specification table.
Overvoltage Category
Class II
This spec is not available in the specification table.
Relative Humidity
0…95 %
This spec is not available in the specification table.
Operating Altitude
0...2000 m without derating 2000 m...5000 m with derating
This spec is not available in the specification table.
Power Dissipation Per Pole
17.6 W
This spec is not available in the specification table.
[Ics] Rated Service Short-Circuit Breaking Capacity
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
This spec is not available in the specification table.
Mounting Position
Horizontal and vertical Flat on the back
This spec is not available in the specification table.
[Icu] Rated Ultimate Short-Circuit Breaking Capacity
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 15 kA at 600 V AC 50/60 Hz conforming to UL 508
This spec is not available in the specification table.
Long-Time Pick-Up Adjustment Type Ir (Thermal Protection)
Adjustable 9 settings
This spec is not available in the specification table.
[Ir] Long-Time Protection Pick-Up Adjustment Range
100...250 A
This spec is not available in the specification table.
Long-Time Protection Delay Adjustment Type Tr
Fixed
This spec is not available in the specification table.
[Tr] Long-Time Protection Delay Adjustment Range
400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir
This spec is not available in the specification table.
Instantaneous Protection Pick-Up Adjustment Type Ii
Fixed
This spec is not available in the specification table.
[Ii] Instantaneous Protection Pick-Up Adjustment Range
3000 A
This spec is not available in the specification table.
Neutral Protection Settings
0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)
This spec is not available in the specification table.
Short-Time Protection Pick-Up Adjustment Type Isd
Adjustable 9 settings
This spec is not available in the specification table.
[Isd] Short-Time Protection Pick-Up Adjustment Range
1.5...10 x Ir
This spec is not available in the specification table.
Short-Time Protection Delay Adjustment Type Tsd
Fixed
This spec is not available in the specification table.
Zone Selective Interlocking Zsi
Without
This spec is not available in the specification table.
Product Description
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Circuit Breaker from SCHNEIDER ELECTRIC
Source & compare similar products
More from Circuit Breaker
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top
Image