Shopping List
Shopping List
MYR - RM
Image
/
/
Schneider Electric LADR0 Time Delay Auxiliary Contact Block, Tesys Deca, 1NO+1NC, Off Delay 0.3-3s, Front, Screw Clamp Terminals
Schneider Electric LADR0 Time Delay Auxiliary Contact Block, Tesys Deca, 1NO+1NC, Off Delay 0.3-3s, Front, Screw Clamp Terminals
Image
Image
Product Description

Schneider Electric LADR0 Time Delay Auxiliary Contact Block, Tesys Deca, 1NO+1NC, Off Delay 0.3-3s, Front, Screw Clamp Terminals


TeSys Deca time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 0.3-3s, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).

Main

  • Range: TeSys, TeSys Deca
  • Product name: TeSys Deca
  • Product or component type: Time delay auxiliary contact block
  • Range compatibility:
    • TeSys Deca CAD
    • TeSys Deca LC1D
    • TeSys F LC1F
    • TeSys F CR1F
  • Mounting location: Front
  • Pole contact composition: 1 NO + 1 NC
  • Contacts operation: Time delay
  • Timer type: Off delay
  • Time delay range: 0.3...3 s
  • [Ue] rated operational voltage: 690 V AC 25...400 Hz
  • [Ie] rated operational current:
    • 6 A at 120 V AC-15
    • 1.04 A at 690 V AC-15
    • 0.55 A at 125 V DC-13
    • 0.1 A at 600 V DC-13
  • [Ui] rated insulation voltage:
    • 690 V conforming to IEC 60947-5-1
    • 600 V conforming to UL 60947-5-1
    • 600 V conforming to CSA C22.2 No 60947-5-1
  • [Ith] conventional free air thermal current: 10 A (at 60 °C)
  • Standards:
    • EN/IEC 60947-5-1
    • UL 60947-5-1
    • CSA C22.2 No 60947-5-1
    • GB/T 14048.5
    • EN 50012
  • Product certifications:
    • IECEE CB Scheme
    • UL
    • CSA
    • CCC
    • EAC
    • UKCA

Complementary

  • Irms rated making capacity:
    • 140 A AC conforming to IEC 60947-5-1
    • 250 A DC conforming to IEC 60947-5-1
  • Permissible short-time rating:
    • 100 A 60 °C 1 s
    • 120 A 60 °C 500 ms
    • 140 A 60 °C 100 ms
  • Protection type: GG fuse 10 A
  • Mechanical durability: 5 Mcycles
  • Minimum switching current: 5 mA
  • Minimum switching voltage: 17 V
  • Non-overlap time:
    • 1.5 ms on de-energisation no overlap between NC and NO contact
    • 1.5 ms on energisation no overlap between NC and NO contact
  • Insulation resistance: > 10 MOhm
  • Connections - Terminals
    • Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
    • Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
    • Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
    • Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
    • Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid
    • Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid
    • Screw clamp terminals
  • Tightening torque:
    • 1.7 N.m - with screwdriver flat Ø 6 mm
    • 1.7 N.m - with screwdriver Philips No 2
    • 1.7 N.m - with screwdriver pozidriv No 2
  • Height: 48 mm
  • Width: 44 mm
  • Depth: 61 mm
  • Colour: Dark grey

Environmental

  • Environmental characteristic: Normal environment
  • IP degree of protection: IP20 conforming to IEC 60529
  • Protective treatment: TH conforming to IEC 60068
  • Ambient air temperature for storage: -60…80 °C
  • Ambient air temperature for operation: -40…70 °C
  • Operating altitude: 3000 m
RM 371.50
Quantity:
EA
This item is sold by
Image
MY-0408537236
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Time Delay Contact Block from SCHNEIDER ELECTRIC
Source & compare similar products
More from Time Delay Contact Block
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top
Image